About cookies on this site Our websites require some cookies to function properly (required). In addition, other cookies may be used with your consent to analyze site usage, improve the user experience and for advertising. For more information, please review your options. By visiting our website, you agree to our processing of information as described in IBM’sprivacy statement. To provide a smooth navigation, your cookie preferences will be shared across the IBM web domains listed here.
Publication
ITherm 2006
Conference paper
Direct liquid jet-impingement cooling with micronsized nozzle array and distributed return architecture
Abstract
We demonstrate submerged single-phase direct liquid-jet-impingement cold plates that use arrays of jets with diameters in the range of 31 to 126 μm and cell pitches from 100 to 500 μm for high power-density microprocessor cooling applications. Using parallel inlet and outlet manifolds, a distributed return concept for easy scaling to 40,000 cells on an area of 4 cm2 was implemented. Pressure drops < 0.1 bar at 2.5 1/min flow rate have been reached with a hierarchical tree-like double-branching manifold. Experiments were carried out with water jets having Reynolds numbers smaller than 900 at nozzle to heater gaps ranging between 3 to 300 μm. We identified four flow regimes, namely, pinch-off, transition, impingement, and separation, with different influences on heat-removal and pressure-drop characteristics. Parametric analysis resulted in an optimal heat-removal rate of 420 W/cm 2 using water as a coolant. For a near optimal design with a gap to inlet diameter ratio of 1.2, we measured a heat-transfer coefficient of 8.7 W/cm2K and a junction to inlet fluid unit thermal resistance of 0.17 Kcm2/W (720 μm chip), which is equivalent to a 370 W/cm 2 cooling performance at a junction to inlet fluid temperature rise of 63°C, a pressure drop of 0.35 bar, and a flow rate of 2.5 1/min. © 2006 IEEE.